System architecture

The generator or the grid
in support of solar pumping

The photovoltaic array provides the main production. When solar power becomes insufficient, the grid or a generator maintains the required operation under the conditions foreseen by the study. Three architectures in the LE LAB catalogue accept this backup source, with different connection and control arrangements.

SQFlex: IO 101 B box SP and SPE: AC input of the RSI PSk3: built-in AC input Solar share calculated month by month
The need

What a second source adds to a solar installation

An installation may have to hold a pressure at the sprinkler, the gun or the centre pivot, hold a flow throughout the watering window, or reach a programmed daily volume. When the solar resource does not supply all the power drawn, the second source tops up the supply. The study then states the solar share, the energy required from the backup source and the operating conditions of the chosen architecture.

This logic is that of constant pressure: as soon as the setpoint becomes an agronomic requirement, it stops being a seasonal average. The kiwi case study in South-West France gives a full-scale reading of it.

Pressurethe setpoint is held during the window defined for the watering device
Flowthe second source tops up solar to hold the flow required
Volumethe programming can continue pumping until the daily volume set is reached
Seasonthe backup source works mainly when the window exceeds the length of the day
The architectures

Three architectures for adding a backup source

Each range organises the backup source in its own way, and each manufacturer's booklet describes the entry point of the second source as well as the control arrangement that goes with it; LE LAB reproduces that description as it stands. The choice between the three follows the pump, and the pump follows the operating point: the flow at the total dynamic head of the site designates the range, and the backup source is fitted afterwards.

RangeEntry point of the second sourceWhat the manual documents
Grundfos SQFlexIO 101 or IO 101 B switching boxthe installation starts when the generator starts, and the box returns automatically to solar as soon as it stops
Grundfos SP and SPE on an RSITerminals L1, L2, L3 of the converter, three-phasethe grid or a generator connected as a backup supply in case of interruptions of the solar array
LORENTZ PSk3AC input built into the controllerswitching between the two energy sources and combining them, for a flow or a pressure independent of the solar resource
Architecture 1

SQFlex: the automatic return to solar

The MSF 3 motor of the SQFlex carries its own control module and accepts both a direct supply of 30 to 300 VDC (100 to 300 VDC for the 2,500 W motor) and a single-phase alternating supply of 1 × 90 to 240 V, at 50 or 60 Hz. The pump can therefore receive the photovoltaic array and an alternating source without an intermediate converter.

The IO 101 box controls the supply of a SQFlex installation paired with a generator. Starting the generator puts the system into operation; stopping it triggers the automatic return to the solar supply. The manual puts it this way: “The generator must run steadily for the pump to start.”

1 × 90-240 Valternating range accepted by the MSF 3 motor, at 50 or 60 Hz
30-300 VDCdirect range of the same motor, on the photovoltaic array side
1,400 Wthe domain of the IO 101; the IO 101 B takes over up to 2,500 W
230 or 115 Vthe two versions of the IO 101, according to the country's grid; the IO 101 B exists only in 230 V
Architecture 2

SP and SPE on an RSI: the backup supply input

The RSI solar converter is compatible with direct current and with alternating current. Its technical booklet puts it in one sentence: the RSI can be connected to the grid or to a generator as a backup supply in case of interruptions of the solar array. This happens on three terminals, L1, L2 and L3, described as the three-phase AC power supply, alongside the direct bus that receives the array.

The alternating input voltage follows the version of the converter: 208 to 240 VAC in the low-voltage range, 380 to 480 VAC in the high-voltage range, that of the large machines. The input is documented as a backup supply, and the organisation of the control is defined at the cabinet, site by site, with the switchgear chosen by the installer. The same compatibility serves the workshop: the booklet notes that it makes it possible to connect the converter to the workshop three-phase supply to prepare it off site, which makes installation quick and simple on site.

This is the architecture of large volumes, that of the SPE and SP pumps on an RSI. Solar pumping on a grid connection finds here its most direct case: a connected farm keeps its supply contract in reserve and lets the array work the rest of the time.

Architecture 3

PSk: the continuous combination of the two sources

The PSk3 controller has a built-in alternating input. It can switch between solar energy and the alternating source or combine the two to hold a flow or a pressure. In hybrid mode, the controller adapts the contribution of the backup source to the variations of the photovoltaic array in order to keep the setpoint foreseen by the sizing.

The two sources meet on the direct bus. To allow them to work simultaneously, the real Vmp of the array must stay above the rectified alternating voltage. On the PSk2 generation, this function is carried by the smartPSUk2 cabinet. The voltage thresholds, the ranges and the connection rules are detailed on the LORENTZ PSk hybrid page.

The control mode is set once and for all at commissioning. The LORENTZ application note “solar by default” describes the result: the operator switches on the generator and the system goes into hybrid mode; the operator switches it off and the system returns to solar mode, automatically. The smartStart adds control of the generator itself, through a volt-free contact that closes as soon as the backup source is called.

On the grid side, the PSk3 works from 380 to 480 V at plus or minus 10%, from 45 to 60 Hz: it monitors the voltage and connects when it sits within this range. The detail of PSk hybrid operation is set out on a separate page.

The worked example

Granada: an example of the split between solar and the backup source

For a need of 60 m³ a day, six hours of sprinkling at 3.0 bar and a total dynamic head of 96 m, the study selects a LORENTZ PSk3-15 C-SJ17-18, an array of 8,755 Wp and a generator of 6.5 kW at continuous load. The energy split is established on sixteen years of real solar resource, hour by hour.

90%of the volume pumped over the year is held by the sun
965 kWh/yrof energy supplied by the backup source, concentrated from November to April
569 h/yrof generator running, spread over the overcast days and the short months
338 L/yrof diesel estimated, on the stated assumption of 0.35 L/kWh at part load
Read the full study: the constant-pressure solar pumping page sets out all the input data, the solution, the month-by-month split and the typical day in November. This page keeps only the values needed to choose and specify the backup source.
The backup equipment

Choosing the generator on the operating point

The quantity that governs the choice is the continuous power of the generator, the power it delivers at continuous load, and the starting point is the power drawn at the operating point. LORENTZ publishes the rule and illustrates it: 6 kW drawn give a 9 kW generator in the hybrid sizing note, and 29.7 kW drawn give 44.55 kW, therefore at least 45 kW, in the Spanish irrigation case. The factor of 1.5 covers the converter efficiency, the power factor and the derating in continuous service. In Granada, the 4.26 kW drawn give 6.5 kW once rounded up to the next half kilowatt.

The controller works with generators whose continuous power is higher, equal to or lower than that of the motor: when the generator is smaller, a speed limit set at commissioning adjusts the demand to what it can deliver. This is the specific gain of the hybrid architecture, written as such in the smartSolution note: it allows a generator markedly more compact than the one a pumping system running on diesel alone would call for.

  • Voltage. 380, 400, 415, 440, 460 or 480 V three-phase, according to the specifications supported by LORENTZ smartSolution.
  • Frequency. 50 or 60 Hz.
  • Remote start. Two-wire function as soon as the smartStart controls the generator; the smartStart supplies a volt-free contact, with a breaking capacity of 250 VAC or 30 VDC at 2 A (PSk2 manual, 2023 edition).
  • Input current. The alternating input works as a rectifier and draws a non-sinusoidal current, which slightly raises the maximum value: all components are sized on it.
  • Public grid. Where a harmonic distortion limit applies, filters are fitted at the input; they also reduce the rms current drawn from the source.
  • Protections. The input receives its fuse and its manual disconnection, sized on the nominal current of the controller.
A field adjustment: if the generator shows unusual oscillations or vibrations when the hybrid system is launched, the LORENTZ note says to reduce the pump speed until it runs steadily.
In the application

The backup source enters the study at step 6

At step 6, declaring another power source adds the backup source to the project. LE LAB then computes the split between solar and the second source over sixteen years of real solar resource, hour by hour, shows the typical day of the design month and gives the annual solar share. The installation diagram represents the connection point corresponding to the chosen range.

The professional report devotes a whole section to this split: the pressure setpoint and the position of the sensor, then the recommended generator at continuous load, the solar share, the backup energy, the running time and the estimated diesel, with its consumption assumption.

Section 04 of the LE LAB report, constant pressure and backup source: setpoint of 3.0 bar, recommended generator of 6.5 kW at continuous load, solar share of 90%, 965 kWh of backup energy, 569 running hours and 338 litres of diesel per year
Section 04 of the professional report for the Granada study: the setpoint, then the backup source, every line with its figure and its assumption written out plainly.
Study an installation with a backup source: the application sizes the pump, the photovoltaic array and the second source from the project data. The constant pressure page details the setpoint, the sensor, the watering window and the flow to be held.
Sources

The documents behind this page

Every equipment behaviour described here comes from the official documentation of the manufacturer concerned. The figures of the worked example come from the LE LAB application, on the hourly PVGIS SARAH2 database.

  • Grundfos, SQFlex, technical manual (92915148, 02.2023, French edition): MSF 3 motor, IO 101 and IO 101 B boxes, “SQFlex solaire avec groupe électrogène” application.
  • Grundfos, RSI, Renewable Solar Inverter for pump control 1.5-250 kW (98462976, 04.2024), technical booklet: AC and DC compatibility, backup supply, workshop preparation.
  • Grundfos, RSI, AC Drives, installation and operating instructions (99116147): alternating input voltages, terminals L1, L2, L3.
  • LORENTZ, PSk3 manual (French edition): solar-diesel sizing, hybrid wiring, input current and harmonics, grid operation.
  • LORENTZ, PSk2 pumping systems manual, 2023 edition: volt-free contact of the smartStart, 250 VAC or 30 VDC at 2 A.
  • LORENTZ, application note PSk2, smartPSUk2 hybrid system layout and design: factor of 1.5, example at 6 kW, procedure in case of oscillation.
  • LORENTZ, application note smartSolution hybrid pumping: blending of the two energy sources, more compact generator, speed limit.
  • LORENTZ, application note Solar by Default Operation: hybrid mode when the generator starts, automatic return to solar when it stops.
  • LORENTZ, application note Hybrid Irrigation in Spain: calculation 29.7 kW × 1.5.
  • LE LAB, study of 11 August 2026: Granada, 60 m³/day, sprinkler at 3.0 bar, six hours, 55 m borehole.